配電柜合不上閘的相關處理

文章來源:http://m.ymmgjx.net/?? 作者:電纜橋架廠家發布時間:2022-07-18?瀏覽次數:12

返回:行業動態
很多設備在運行過程中都免不了要出現故障,當配電柜出現故障的時候,能否可以及時有效的處理就是對做運維技術的考驗了。下面就來簡單了解一番吧。
Many equipment will inevitably fail during operation. When the power distribution cabinet fails, whether it can be handled in time and effectively is the test of operation and maintenance technology. Now let's have a brief look.
(1)操作不當。
(1) Improper operation.
(2)合閘電源消失。
(2) The closing power supply disappears.
(3)控制回路斷線。
(3) The control circuit is disconnected.
(4)轉換開關接觸不良。
(4) The change-over switch is in poor contact.
(5)合閘線圈斷線。合閘接觸器線圈斷線。
(5) The closing coil is disconnected. The coil of closing contactor is disconnected.
(6)輔助觸點接觸不良。
(6) Poor contact of auxiliary contact.
(7)其它機械方面故障,如傳動機構連桿脫落、合閘鐵芯卡澀,斷路器分閘后機構沒有復位等。
(7) Other mechanical faults, such as the falling off of the connecting rod of the transmission mechanism, the jamming of the closing iron core, and the failure of the mechanism to reset after the opening of the circuit breaker.
處理方法:
Treatment method:
(1)在綠燈亮的情況下,再合一次閘,如果合上,說明是轉換開關沒合到位,屬于操作不當。
(1) When the green light is on, close the switch again. If it is closed, it means that the change-over switch is not closed in place, which belongs to improper operation.
(2)如果綠燈亮,接觸器動作,應該檢查合閘電源是否正常,如電源開關沒投、合閘熔斷器熔斷等原因并處理。檢查熔斷器是否熔斷的方法有兩種:一種為帶電檢查,一種為取下后用歐姆檔檢查。
(2) If the green light is on and the contactor acts, check whether the closing power supply is normal, such as the failure of the power switch and the fusing of the closing fuse, and deal with it. There are two methods to check whether the fuse is fused: one is live inspection, and the other is to check with Ohm gear after removal.
山東電纜橋架
(3)如果綠燈不亮,那么首先檢查控制熔斷器和小開關是否熔斷或者跳閘。若果發現問題,應及時更換。
(3) If the green light is not on, first check whether the control fuse and small switch are fused or tripped. If any problem is found, it should be replaced in time.
(4)輔助觸點接觸不良,綠燈不亮,打開機構蓋,檢查合閘回路輔助觸點,調整小拉桿到合格位置。什么位置算合格?
(4) The auxiliary contact is poor and the green light is not on. Open the mechanism cover, check the auxiliary contact of the closing circuit, and adjust the small pull rod to the qualified position. What position is qualified?
(5)合閘接觸器線圈斷線,或者接點卡勁。更換接觸器或者拆下檢修。
(5) The coil of the closing contactor is disconnected, or the contact is jammed. Replace the contactor or remove it for maintenance.
(6)轉換開關接觸不良,用短路線將5-8接點短路后能合閘,說明接點接觸不良,拆檢修或者更換。
(6) If the change-over switch has poor contact, it can be closed after short circuiting the 5-8 contact with a short circuit, which indicates that the contact has poor contact, and it should be removed for maintenance or replacement.
(7)打開機構蓋,用手動合閘檢查合閘頂桿是否能過托架2mm,如果不能說明合閘鐵芯行程不夠,應調整鐵芯頂桿長度。
(7) Open the mechanism cover and check whether the closing ejector rod can pass the bracket by 2mm with manual closing. If it cannot be explained that the stroke of the closing iron core is not enough, the length of the iron core ejector rod should be adjusted.
(8)打開機構蓋,檢查機構在上一次分閘后是否回位。如果沒有,應手動方法將其歸位,再合閘。
(8) Open the mechanism cover and check whether the mechanism returns after the last opening. If not, it should be manually reset and reclosed.
(9)山東電纜橋架廠家建議檢查合閘電源電壓是否滿足不低于85%的額定電壓。
(9) Shandong cable tray manufacturer suggests to check whether the closing power supply voltage meets the rated voltage of no less than 85%.
配電柜合不上閘的相關處理問題便是這樣了,如果您這邊還有什么問題要了解的話,就來關注我們網站http://m.ymmgjx.net咨詢吧!
This is how to deal with the problem that the power distribution cabinet can't close the switch. If you have any questions to understand, please pay attention to our website http://m.ymmgjx.net Consult!
工程案例 / Case Show
  • 濟南火車站 濟南火車站
  • 曲阜孔子文化會展中心 曲阜孔子文化會展中心
  • 山東工藝美院 山東工藝美院
  • 公安廳服務展示 公安廳服務展示
推薦資訊 / Recommended news
  • 梯式橋架:工業動力的“呼吸”骨架梯式橋架:工業動力的“呼吸”骨架

    在建筑電氣與工業廠房的龐大系統中,電纜橋架猶如人體的血管,負責輸送持續供應的動力與信號。而在眾多橋架類型中,梯式橋架憑借其獨特的結構設計,成為了大截面動力電纜的絕佳載體。In the vast sys

    TIME:2026-06-22