山東電纜橋架的使用對于我們的整個建筑行業(yè)來說,都有著重要的作用和價值,對于增加項(xiàng)目的便利性等方面,都有很大的優(yōu)勢!那么下面就來了解下建筑橋架的支吊架、吊架的安裝內(nèi)容。
The use of cable bridge in Shandong Province plays an important role and value for our entire construction industry, and has great advantages in increasing the convenience of the project! Then let's understand the installation contents of the supports and hangers of the building bridge.
支架和吊架所使用的鋼應(yīng)該是直立的,并且沒有明顯的扭曲。下部材料長度偏差應(yīng)在3mm以內(nèi),切口不能有卷邊和毛刺。
The steel used for supports and hangers shall be upright and free from obvious distortion. The length deviation of the lower material shall be within 3mm, and the cut shall be free of curling and burr.
鋼支架和吊架應(yīng)焊接牢固,無明顯變形,支架和鐵件焊接前厚度大于4mm應(yīng)打坡口,焊縫均勻平整,焊縫長度符合要求,不能有裂紋、咬邊、氣孔、凹陷、漏焊等缺陷。
The steel support and hanger shall be welded firmly without obvious deformation. Before welding, the support and iron parts shall be beveled with a thickness of more than 4mm. The weld shall be uniform and flat, and the weld length shall meet the requirements. There shall be no cracks, undercuts, pores, depressions, missing welds and other defects.
支架和吊架應(yīng)安裝牢固,保證水平和垂直,在有斜坡的建筑物上安裝支架和吊架,其高度和角度應(yīng)與建筑物的斜坡和角度一致。
The support and hanger shall be installed firmly to ensure horizontal and vertical. The support and hanger shall be installed on the building with slope, and its height and angle shall be consistent with the slope and angle of the building.
支架和吊架的規(guī)格一般不能小于扁鋼30mm×3mm;角鋼25mm×25mm×3mm。
The specification of support and hanger shall not be less than 30mm of flat steel × 3mm; Angle steel 25mm × 25mm × 3mm。

嚴(yán)禁用電氣焊對鋼結(jié)構(gòu)或輕鋼龍骨的任何部位進(jìn)行切割。
It is forbidden to cut any part of steel structure or light steel keel by electric welding.
通用吊具應(yīng)采用定型產(chǎn)品,應(yīng)有各自獨(dú)立的吊卡或支撐系統(tǒng)。
The general lifting appliance shall adopt the finalized product and shall have its own independent elevator or support system.
固定支點(diǎn)的間距一般不大于1.5~3米,室外立柱的跨度一般為6米。出入接線盒、箱柜、轉(zhuǎn)角處、拐角處和變形縫的三端500mm以內(nèi)及丁字節(jié)連接處應(yīng)設(shè)置固定支撐點(diǎn)。非線段的支吊架配置應(yīng)遵循以下原則。當(dāng)橋架寬幅小于300mm時,應(yīng)在支吊架的支吊架側(cè)面與支吊架的直線段為300~600mm的直線段。當(dāng)橋架寬度大于300mm時,除了滿足以上要求外,在非直線段的中間還應(yīng)增設(shè)支吊架。
The spacing of fixed fulcrums is generally not more than 1.5~3 meters, and the span of outdoor columns is generally 6 meters. Fixed support points shall be set within 500mm of the three ends of the junction box, box, cabinet, corner, deformation joint and T-joint. The following principles shall be followed for the support and hanger configuration of non-section. When the width of the bridge is less than 300 mm, the straight section between the side of the support and the hanger and the support and hanger shall be 300~600 mm. When the width of the bridge is greater than 300mm, in addition to meeting the above requirements, supports and hangers shall be added in the middle of the non-linear section.
以上就是有關(guān)山東電纜橋架的全部內(nèi)容了,希望各位能參考我們
http://m.ymmgjx.net上面給出的內(nèi)容,這樣在今后的使用和應(yīng)用過程中一定會有所幫助的!
That's all about Shandong cable bridge. I hope you can refer to us http://m.ymmgjx.net The content given above will be helpful in the future use and application process!