有時由于各種外界原因,不同的電纜需要放到同一橋架中,為了保證電纜之間的信號互相不受干擾,就需要在橋架中間增加隔板,那么槽式電纜橋架的使用是否可以加隔板?
Sometimes, due to various external reasons, different cables need to be placed in the same bridge. In order to ensure that the signals between cables are not interfered with each other, partition plates need to be added in the middle of the bridge. Can partition plates be added in the use of trough cable bridge?
槽式電纜橋架不適合敷設在熱力管道的上方或者腐蝕性液體管道的下方。當管道氣體的密度大于空氣時,槽式電纜橋架宜安裝在其上方,當管道氣體的密度小于空氣時,槽式電纜橋架適合安裝在其下方。下面北京電纜橋架小編就給大家介紹一下槽式電纜橋架及隔板的內容。
The trough type cable tray is not suitable for laying above the heat pipe or below the corrosive liquid pipe. When the density of pipeline gas is greater than that of air, the trough type cable tray should be installed above it. When the density of pipeline gas is less than that of air, the trough type cable tray is suitable to be installed below it. Next, the Beijing cable tray editor will introduce the contents of trough cable tray and bulkhead.
槽式電纜橋架與一般工藝管道平行鋪設時,敷設間隔少400mm,與工藝管道交叉敷設時,安裝間距小為300mm,槽式電纜橋架與腐蝕氣體管道的平行間距少為500mm,交叉間距小為500mm。槽式電纜橋架的安裝應該依據(jù)電氣施工圖紙,對電纜橋架的走向進行測量,適宜采用標準產(chǎn)品和工廠預制件。槽式電纜橋架的分段應該合理,兩段連接位置不應該放在穿墻和跨越樓層孔洞處。
When the trough cable tray is laid in parallel with the general process pipe, the laying interval shall be at least 400mm. When it is laid in cross with the process pipe, the installation interval shall be less than 300mm. The parallel interval between the trough cable tray and the corrosive gas pipe shall be at least 500mm, and the cross interval shall be less than 500mm. The installation of trough type cable tray should measure the direction of cable tray according to the electrical construction drawings, and it is suitable to use standard products and factory prefabricated parts. The sections of the trough type cable tray should be reasonable, and the connection position of the two sections should not be placed at the hole through the wall and across the floor.

鍍鋅托盤或梯架兩節(jié)進行槽式電纜橋架安裝時,中間的連接片如果不用跨接線,則需要在其兩端安裝不少于2個帶防松螺帽或防松墊圈的固定螺栓。槽式電纜橋架安裝的托盤和梯架為非鍍鋅材質時,兩節(jié)橋架中間連接板的兩端,應采用截面積>=4平米毫米的銅芯跨接線進行連接。
When installing the trough type cable tray with two sections of galvanized tray or ladder, if the connecting strip in the middle does not use jumper wire, it is necessary to install at least 2 fixing bolts with anti loose nuts or anti loose washers at both ends. When the tray and ladder installed on the trough cable tray are made of non galvanized material, the two ends of the middle connecting plate of the two cable trays shall be connected with copper core jumper wires with a sectional area of > =4 square meters.
山東電纜橋架廠家提醒,如果把高壓電纜和低壓電纜敷設在同一槽式電纜橋架,該橋架就需要在中間增加隔板,以防止兩種電纜信號互相干擾,如果把電力電纜和信號電纜放在同一槽式電纜橋架內,也需要在中間加隔板。如果把3種不同性質的電纜放在同一槽式電纜橋架內,則橋架中間需要加2個隔板。
Shandong cable tray manufacturer reminds that if the high-voltage cable and low-voltage cable are laid in the same trough cable tray, a partition needs to be added in the middle of the tray to prevent the two cable signals from interfering with each other. If the power cable and signal cable are placed in the same trough cable tray, a partition also needs to be added in the middle. If three kinds of cables with different properties are placed in the same trough cable tray, two diaphragms need to be added in the middle of the tray.
The above is about whether the trough cable tray is equipped with a partition. If you have any questions about the relevant knowledge, you can pay attention to our website http://m.ymmgjx.net , or contact us directly for field investigation.